APPENDIX C: TECHNICAL SPECIFICATIONS

C.1 Compliance to Standards
   
CSA C22.2 No. 205-M1983 Signal Equipment
         Consumer and Commercial Products
    
CSA C22.2 No. 0.4-M1993 Bonding and Grounding of
         Electrical Equipment Protective Grounding

C.2 Operating Temperature Range: -20 C to + 60

C. C.3 Input Power Supply
     
C.3.1 100V - 125V AC / 60 Hz (mains supply)
      C.3.2 8 to 16 V DC (battery)

C.4 High Voltage Input - Is designed to be connected ONLY to a fence energizer output.
     Impedance: 20,000 ohm.
     Pulse Interval: 0.9 - 1.4 seconds
     Pulse Energy: max 10 Joules
     Pulse Voltage: max 11,000 V

C.5 Rating of the switched AC power supply outlet for the fence energizer.
     Voltage:           same as input power supply
     Current:           1 A continuous, with fuse protection

C.6 Rating of the switched DC power supply output for the fence energizer.
      Voltage: same as input power supply C.3.2
      Current: 1.35 A continuous, with fuse protection

C.7 Light Alarm Output: Switched / Continuous on until reset.
     Voltage: same as input power supply C.3.2
     Current: 0.65 A continuous, with fuse protection

C.8 Siren Alarm Output: Switched / Limited time operations due to regional and local audible noise pollution regulations.
     Voltage: same as input power supply C.3.2
     Current: 0.65 A continuous, with fuse protection

C.9 Auto-Dialer/Wireless Modem Power Supply: Switched / Continuous on until reset.
     Voltage: same as input power supply C.3.2
     Current: 0.65 A continuous, with fuse protection